Installation Manual
Launch & Configuration
Page 9
The first time you launch the Dupline-Online Server, the software is pre-configured to startup most of the
services. Only a minimum of configuration is required to get the Dupline-Online Server up and running. The
required configuration is described in the following. The table below shows all services with a brief
description.
Service name Description
MailHandler
E-mail service used for sending e-mails.
DBProvider
Provides access to the application database (Microsoft SQL Server)
UserManager
Manager for users defined in the system.
DDCApp
The main application service
MsgSender
Sends alarms messages to either the MailHandler or SMSHandler service.
Surveillance Manages surveillance such as triggering of digital channel alarms.
LogIf
Receives and stores log data from the Dupline Data Loggers in the application
database.
SocketComm
Manages communication with the Dupline Data Loggers over Ethernet (TCP/IP
socket)
SMSComm
Manages communication with the Dupline Data Loggers over the GSM network
(SMS)
Jetty
The web server providing access to the web pages.
SMSHandler
Sending and receiving of SMS messages through an attached GSM modem.
The services listed below must always be started. Do not change any of the settings for these services:
DBProvider
UserManager
DDCApp
MsgSender
Surveillance
LogIf
Jetty
To log data over a local area network (LAN) or over the Internet from the Dupline Data Logger through a
serial to Ethernet converter the SocketComm service must be started. If logging over ALN / Ethernet is not
required simply uncheck the Auto start checkbox and stop the service.
To log data from the Dupline Data Logger over the GSM network through SMS messages, the SMSComm
and SMSHandler services must be started. If logging over the GSM network isn’t required, simply uncheck
the Auto start checkbox and stop the SMSComm service.
To enable sending of SMS messages from the Dupline-Online Server, the SMSHandler service must be
started. Notice that this service is also used when logging data over the GSM network as described above.
In the following sections, the services which requires configuration are described. To configure a service
select the service in the service list and click the Config button.